Skip to content
Merged
Show file tree
Hide file tree
Changes from all commits
Commits
Show all changes
19 commits
Select commit Hold shift + click to select a range
c432a87
Blog: How to Stop Noisy Sensor Data from Flooding Your Industrial System
sumitshinde-84 Apr 21, 2026
d6d3902
Merge branch 'main' into deadband
sumitshinde-84 Apr 21, 2026
dcfd9ba
Optimised images with calibre/image-actions
github-actions[bot] Apr 21, 2026
231b847
update blog
sumitshinde-84 Apr 22, 2026
5ed8307
Merge branch 'deadband' of github.com:FlowFuse/website into deadband
sumitshinde-84 Apr 22, 2026
858e0b3
Optimised images with calibre/image-actions
github-actions[bot] Apr 22, 2026
ca85209
Update rollout-edge-health-monitoring-100-devices.md
sumitshinde-84 Apr 22, 2026
7eecc3c
Update rollout-edge-health-monitoring-100-devices.md
sumitshinde-84 Apr 22, 2026
94c7f7a
Update rollout-edge-health-monitoring-100-devices.md
sumitshinde-84 Apr 22, 2026
40d00d3
push tile
sumitshinde-84 Apr 22, 2026
ed83b1d
Merge branch 'deadband' of github.com:FlowFuse/website into deadband
sumitshinde-84 Apr 22, 2026
d7d2981
Optimised images with calibre/image-actions
github-actions[bot] Apr 22, 2026
6dfa6d5
Rename rollout-edge-health-monitoring-100-devices.md to stop-noisy-se…
sumitshinde-84 Apr 22, 2026
9b4be78
Update stop-noisy-sensor-data-deadband-filter-flowfuse.md
sumitshinde-84 Apr 23, 2026
67e1225
update inject node image
sumitshinde-84 Apr 23, 2026
8f4b398
Merge branch 'main' into deadband
sumitshinde-84 Apr 23, 2026
41a5ed4
Optimised images with calibre/image-actions
github-actions[bot] Apr 23, 2026
e2eb4ec
Update stop-noisy-sensor-data-deadband-filter-flowfuse.md
sumitshinde-84 Apr 23, 2026
568181d
Update stop-noisy-sensor-data-deadband-filter-flowfuse.md
sumitshinde-84 Apr 23, 2026
File filter

Filter by extension

Filter by extension

Conversations
Failed to load comments.
Loading
Jump to
Jump to file
Failed to load files.
Loading
Diff view
Diff view
Loading
Sorry, something went wrong. Reload?
Sorry, we cannot display this file.
Sorry, this file is invalid so it cannot be displayed.
Loading
Sorry, something went wrong. Reload?
Sorry, we cannot display this file.
Sorry, this file is invalid so it cannot be displayed.
Binary file added src/blog/2026/04/images/deadband-filter.png
Loading
Sorry, something went wrong. Reload?
Sorry, we cannot display this file.
Sorry, this file is invalid so it cannot be displayed.
Binary file added src/blog/2026/04/images/filter-node-deadband.png
Loading
Sorry, something went wrong. Reload?
Sorry, we cannot display this file.
Sorry, this file is invalid so it cannot be displayed.
Loading
Sorry, something went wrong. Reload?
Sorry, we cannot display this file.
Sorry, this file is invalid so it cannot be displayed.
Loading
Sorry, something went wrong. Reload?
Sorry, we cannot display this file.
Sorry, this file is invalid so it cannot be displayed.
117 changes: 117 additions & 0 deletions src/blog/2026/04/stop-noisy-sensor-data-deadband-filter-flowfuse.md
Original file line number Diff line number Diff line change
@@ -0,0 +1,117 @@
---
title: "How to Stop Noisy Sensor Data from Flooding Your Industrial System"
subtitle: "A practical guide to suppressing sensor noise in industrial systems using FlowFuse"
description: "Learn how to implement a deadband filter in FlowFuse to suppress noisy sensor data from PLCs, temperature probes, and flow meters. Step-by-step guide using the built-in filter node on FlowFuse."
date: 2026-04-23
keywords: deadband filter, sensor noise filtering, industrial data filtering, FlowFuse, industrial sensor data, IIoT data processing, edge data filtering
authors: ["sumit-shinde"]
image: /blog/2026/04/images/stop-noisy-sensor-data.png
tags:
- flowfuse
cta:
type: signup
title: "Start Building Cleaner Industrial Pipelines Today"
description: "FlowFuse makes it easy to connect, filter, and manage industrial sensor data across your entire fleet. Start your free trial and get your first flow running in minutes."
---

In industrial systems, sensors rarely sit perfectly still. A temperature probe, pressure transducer, or flow meter will constantly fluctuate. Not because the process is changing, but because of electrical noise, vibration, or quantization artifacts in the ADC. If your control system reacts to every tiny wiggle, it triggers unnecessary alarms, wears out actuators, and buries real events in a fog of jitter.

<!--more-->

A deadband filter fixes this with a single rule: only report a new value if it has moved beyond a defined threshold from the last accepted reading. Computationally trivial and tunable with one parameter, it is the simplest first line of defense for any industrial sensor pipeline. In this post, we will break down how it works, when to use it, and how to implement one in FlowFuse.

## What is a deadband filter?

A deadband filter is a signal processing technique that suppresses small, insignificant changes in sensor readings. Instead of reporting every value the sensor produces, it only forwards a new reading when the value has changed by more than a defined threshold from the last accepted value. Anything that falls within that band is considered noise and silently discarded.

Think of it like a thermostat. Your home heating does not kick in every time the temperature shifts by 0.1°C. It waits until the temperature drops past a meaningful threshold before reacting. A deadband filter applies the same logic to any continuous sensor signal.

!["Raw sensor data vs deadband-filtered output showing noise suppression in industrial systems"](./images/deadband-filter.png)
*Raw sensor data (left) vs. deadband-filtered output (right). The shaded band shows the deadband zone. The filter only updates when the signal crosses its boundary.*

As shown above, the raw signal on the left is erratic and full of jitter. The filtered output on the right steps cleanly. It only moves when the signal genuinely crosses the deadband boundary, ignoring everything in between.

## How does a deadband filter work?

The logic is straightforward. The filter keeps track of the last value it accepted and compares every new incoming reading against it. If the difference is greater than the deadband threshold, the new value is accepted and passed downstream. If not, it is ignored and the last accepted value is held in place.

!["Flowchart showing deadband filter decision logic — new reading arrives, if change exceeds threshold the value is accepted and forwarded, otherwise it is discarded and the last value is held"](./images/deadband-filter-how-it-works.png)
*Each incoming sensor reading is compared against the last accepted value. Only readings that exceed the deadband threshold are forwarded. Everything else is silently discarded.*

That single comparison is the entire filter. No buffers, no history, no moving averages. Just one stored value and one threshold check per incoming sample.

## Choosing the right threshold

Setting the deadband too narrow lets noise through and defeats the purpose. Setting it too wide causes the filter to miss real process changes or report them too late. The right value sits just above your sensor noise floor.

A practical starting point is to measure your sensor output when the process is known to be stable, observe the peak-to-peak fluctuation, and set your deadband to roughly that value. From there, tune it in the field until alarms and updates reflect only genuine process changes.

## Prerequisites

Before getting started, you will need the following:

- A running FlowFuse instance. If you do not have one yet, start with a [free trial](https://app.flowfuse.com/account/create) and follow [this guide](https://flowfuse.com/blog/2025/09/installing-node-red/) to get up and running on your edge device.
- A sensor or data source publishing values to FlowFuse via MQTT, Modbus, OPC-UA, or a simulated inject node for testing.

## Collecting sensor data with FlowFuse

Before you can filter anything, you need data flowing in. In industrial environments that means connecting to whatever is already on the floor. PLCs, sensors, drives, and controllers that speak dozens of different protocols, many of them decades old.

This is where FlowFuse earns its place. It connects to virtually any industrial data source out of the box. OPC-UA, Modbus, MQTT, Siemens S7, BACnet, and more. No custom drivers, no middleware. Whether your data lives on a modern IIoT sensor or a legacy PLC that has been running since the 1990s, FlowFuse can reach it.

Every reading arrives ready to use. The sensor value lands in `msg.payload` exactly as it was read, and that is all the filter needs to do its job.

Not sure how to connect your specific device or protocol? [Contact us](/contact-us/) and we will help you get your data flowing.

If you are following along and do not have a live sensor available, you can simulate one using an inject node. Set it to repeat on an interval, and use a JSONata expression to generate a noisy value:

```json
$round(45 + (($millis() % 10000) / 1000) + $random(), 2)
```

This simulates a sensor that drifts steadily over time with random noise on top, giving the signal enough range to realistically cross the deadband threshold.

!["Inject node configured as a noisy sensor simulator using JSONata expression in FlowFuse"](./images/noisy-sensor-simulation.png)
*Inject node configured to simulate a noisy sensor, generating a drifting value with added jitter every second.*

## Implementing a deadband filter

FlowFuse has a built-in **filter** node that handles deadband filtering out of the box. No code required. It only passes data when the payload has changed by more than a specified amount, which is exactly what a deadband filter does.

### Step 1: Add the filter node

1. In your palette, search for **filter**.
2. Drag it onto the canvas.

### Step 2: Place it in your flow

1. Position the filter node between your sensor input node and your output node.
2. Wire the sensor input to the filter node input, and the filter node output to your output. Whether that is a dashboard node, a database write node, or an MQTT broker.

### Step 3: Configure the filter node

1. Double-click the filter node to open its settings.
2. Set the **Mode** to `block unless value change is greater than`.
3. Enter your deadband value in the threshold field. You can use an absolute value such as `1.5` or a percentage such as `5%`.
4. Set the comparison to `compared to last input value`. This ensures each new value is compared against the last value that was actually forwarded.
5. Leave the **Property** as `msg.payload` unless your sensor data arrives on a different property.
Comment thread
sumitshinde-84 marked this conversation as resolved.
6. If your flow handles multiple sensors on different topics, check **Apply mode separately for each** and set it to `msg.topic`. This allows a single filter node to handle multiple sensors independently.
7. Click **Done** and deploy your flow.

!["Filter node configuration in FlowFuse showing deadband mode set to block unless value change is greater than threshold"](./images/filter-node-deadband.png)
*Filter node configured in deadband mode with threshold set to 2.5. Only values that differ by more than 2.5 units from the last accepted reading are passed downstream.*

> **Note:** The first value that arrives is always passed through and stored as the reference point. From that point on, every incoming value is compared against it. Only values that differ by more than the threshold are forwarded. When one is, it becomes the new reference point for all comparisons that follow.

!["Side by side dashboard comparison showing filtered vs unfiltered sensor data in FlowFuse"](./images/chart-with-deadband-and-without-it.png)
*The dashboard above shows two charts connected to the same sensor data. The left chart has the deadband filter applied, the right does not. Notice the noise difference.*

## Conclusion

Noisy sensor data is one of those problems that looks small until it is not. False alarms, worn actuators, bloated historian databases, and dashboards that are impossible to read. All of it traces back to the same root cause. A control system reacting to every fluctuation instead of only the ones that matter.

A deadband filter solves this with a single comparison. No complex logic, no additional infrastructure, no performance overhead. Just a threshold and a rule, applied consistently to every incoming reading.

But filtering noise is just one piece of a reliable industrial data pipeline. FlowFuse goes further. It simplifies collecting data from any device or protocol, implementing patterns like deadband filtering, [store and forward](/blog/2025/11/store-and-forward-edge-data-buffering/) to handle network interruptions, [dead letter queues](/blog/2026/03/how-to-implement-dlq-and-retries/) to catch and recover failed messages, and much more. All of it managed centrally, deployed consistently, and running reliably across your entire fleet.

The filter handles the noise. FlowFuse handles everything else.