You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
Copy file name to clipboardExpand all lines: Manuals/FDS_Validation_Guide/Experiment_Chapter.tex
+17-8Lines changed: 17 additions & 8 deletions
Original file line number
Diff line number
Diff line change
@@ -333,21 +333,23 @@ \section{Cable Response to Live Fire -- CAROLFIRE}
333
333
\section{CERTEC Pool Fires}
334
334
\label{CERTEC_Pool_Fires_Description}
335
335
336
-
Pool fire experiments were conducted at the Centre d’Estudis del Risc Tecnol\`{o}gic (CERTEC), Universitat Polit\`{e}cnica de Catalunya, Barcelona, Spain~\cite{Munoz:JHM2007}. The experiments were performed using gasoline and diesel oil as fuel. Five concentric circular pools (1.5, 3, 4, 5 and 6~m in diameter) were used. Five of the experiments have been chosen for study, listed in Table~\ref{CERTEC_Parameters}. Modeling and experimental results are presented in Ref.~\cite{Rengel:JLP2018}.
336
+
Pool fire experiments were conducted at the Centre d’Estudis del Risc Tecnol\`{o}gic (CERTEC), Universitat Polit\`{e}cnica de Catalunya, Barcelona, Spain~\cite{Munoz:JHM2007}. The experiments were performed using gasoline and diesel oil as fuel. Five concentric circular pools (1.5, 3, 4, 5 and 6~m in diameter) were used. Measurements include centerline plume temperature, wide-angle radiant heat flux, emissive power, flame tilt, and flame height.
337
+
338
+
Five of the diesel fuel experiments have been chosen for study, listed in Table~\ref{CERTEC_Parameters}. Modeling and experimental results are presented in Ref.~\cite{Rengel:JLP2018}.
337
339
338
340
\begin{table}[ht]
339
341
\centering
340
342
\caption[Measured properties for the CERTEC Pool Fires]{Measured properties for the CERTEC Pool Fires.}
341
343
\label{CERTEC_Parameters}
342
344
\begin{tabular}{|c|c|c|c|c|}
343
345
\hline
344
-
Experiment & Pool & Wind & Ambient & Radiometer \\
345
-
Name & Diameter (m) & Speed (m/s) & Temperature (\unit{\degreeCelsius}) & Distance (m) \\ \hline\hline
346
-
01$_$D3 & 3 & 2.39 & 12 & 9 \\ \hline
347
-
04$_$D3 & 3 & 0 & 16 & 15 \\ \hline
348
-
14$_$D4 & 4 & 0.43 & 20 & 12 \\ \hline
349
-
10$_$D5 & 5 & 1.02 & 16 & 15 \\ \hline
350
-
07$_$D6 & 6 & 1.10 & 19 & 18 \\ \hline
346
+
Experiment & Pool & Wind & Ambient & Radiometer \\
347
+
Name & Diameter (m) & Speed (m/s) & Temperature (\unit{\degreeCelsius}) & Distance (m) \\ \hline\hline
348
+
01\_D3 & 3 & 2.39 & 12 & 9 \\ \hline
349
+
04\_D3 & 3 & 0 & 16 & 15 \\ \hline
350
+
14\_D4 & 4 & 0.43 & 20 & 12 \\ \hline
351
+
10\_D5 & 5 & 1.02 & 16 & 15 \\ \hline
352
+
07\_D6 & 6 & 1.10 & 19 & 18 \\ \hline
351
353
\end{tabular}
352
354
\end{table}
353
355
@@ -2649,6 +2651,13 @@ \section{Restivo Compartment Air Flow Experiment}
Sandia National Laboratories conducted experiments in support of siting requirements for Liquefied Natural Gas (LNG) facilities~\cite{Luketa:11078}. The experiments involved jet fires, pool fires, fireballs, and concrete walls that could serve as thermal barriers. The fuels tested include ethane, ethylene, propane, and isopentane. The jet fires are considered moderate in scale with projected flame lengths up to 17.3~m and exit mass flow rates up to 2.3~kg/s. The pool fires and fireballs are considered large scale with a pool diameter of 5~m and maximum effective diameter up to 78~m, respectively. Measurements for the fire experiments include flame geometry, heat flux external to the fire, surface emissive power, and in the case of fireballs, rise height and duration. Data was also collected for model parameter inputs such as atmospheric conditions that include wind speed, wind direction, temperature, pressure, and relative humidity, as well as the conditions of the fuel supply.
0 commit comments