Smart Full Discovery Audit v2

Findings

The previous patch still depended too much on whatever the ARIEC61850 high-level model builder returned. When that layer only produced the first readable MMXU branch, ARServer's wizard still showed only MMXU1 even though the IED's MMS directory contained many logical-node instances.

This is not a valid gateway architecture. ARServer must first build an IED inventory as completely as IEDScout does, then filter that inventory into SCADA-friendly signals. It must never synthesize MMXU1..24 from vendor assumptions.

Fixes in this patch

  1. Removed the idea of vendor/MMXU count profile from the active discovery path.
  2. Added a supplemental read-only MMS GetNameList directory browse using the clean-room MMS session.
    • It merges domain named variables and named variable lists with the ARIEC61850 discovery snapshot.
    • If the IED rejects a second client association, discovery continues with the primary ARIEC61850 snapshot.
  3. Added generic ARIEC61850 object-shape logical-node extraction.
    • This detects LN instances exposed as separate properties, such as LnClass = MMXU and InstanceNumber = 2.
    • It combines class and instance into MMXU2 without hardcoding a range.
  4. Wizard report selection UI is removed.
    • Step 3 is now read-only Auto Report Plan Review.
    • Users select signals only; ARServer maps signal -> DataSet -> RCB -> polling fallback automatically.
  5. Signal selection UX improved.
    • Header checkbox selects/deselects all visible publishable signals.
    • Grid uses Extended row selection.
    • Ctrl/Shift row selection works through WPF selection.
    • Checkbox click applies to selected rows; Shift-click checkbox applies a block selection.

Expected Moxa/GD7700 behavior

If the IED's MMS directory exposes MMXU2, MMXU3, ... as named variables or logical-node objects, the wizard should now show those instances. If it still shows only MMXU1, the remaining issue is in the connected ARIEC61850 discovery/runtime library or the clean-room GetNameList association was rejected by the IED. In that case Diagnostics should be checked for supplemental names in the Native Discovery summary.