| 1 | +# DEVICE:URL:REPORT: https://github.com/networkupstools/nut-ddl/pull/40 |
| 2 | + |
| 3 | +# DEVICE:COMMENT: |
| 4 | +# Device dump generated by ./nut-ddl-dump.sh on Sat, 16 Mar 2024 15:42:38 +0100 |
| 5 | +# DEVICE:EOC |
| 6 | + |
| 7 | +# :; upsc ups |
| 8 | +battery.charge: 100 |
| 9 | +battery.charge.low: 10 |
| 10 | +battery.charge.warning: 50 |
| 11 | +battery.date: 2001/09/25 |
| 12 | +battery.mfr.date: 2022/12/13 |
| 13 | +battery.runtime: 1572 |
| 14 | +battery.runtime.low: 120 |
| 15 | +battery.type: PbAc |
| 16 | +battery.voltage: 13.5 |
| 17 | +battery.voltage.nominal: 12.0 |
| 18 | +device.mfr: American Power Conversion |
| 19 | +device.model: Back-UPS ES 850G2 |
| 20 | +device.serial: 5B2250T99999 |
| 21 | +device.type: ups |
| 22 | +driver.name: usbhid-ups |
| 23 | +driver.parameter.pollfreq: 30 |
| 24 | +driver.parameter.pollinterval: 2 |
| 25 | +driver.parameter.port: auto |
| 26 | +driver.parameter.synchronous: auto |
| 27 | +driver.version: 2.8.0 |
| 28 | +driver.version.data: APC HID 0.98 |
| 29 | +driver.version.internal: 0.47 |
| 30 | +driver.version.usb: libusb-1.0.26 (API: 0x1000109) |
| 31 | +input.sensitivity: medium |
| 32 | +input.transfer.high: 266 |
| 33 | +input.transfer.low: 180 |
| 34 | +input.voltage: 238.0 |
| 35 | +input.voltage.nominal: 230 |
| 36 | +ups.beeper.status: enabled |
| 37 | +ups.delay.shutdown: 20 |
| 38 | +ups.firmware: 938.a2 .I |
| 39 | +ups.firmware.aux: a2 |
| 40 | +ups.load: 18 |
| 41 | +ups.mfr: American Power Conversion |
| 42 | +ups.mfr.date: 2022/12/13 |
| 43 | +ups.model: Back-UPS ES 850G2 |
| 44 | +ups.productid: 0002 |
| 45 | +ups.realpower.nominal: 520 |
| 46 | +ups.serial: 5B2250T07387 |
| 47 | +ups.status: OL |
| 48 | +ups.test.result: No test initiated |
| 49 | +ups.timer.reboot: 0 |
| 50 | +ups.timer.shutdown: -1 |
| 51 | +ups.vendorid: 051d |
| 52 | + |
| 53 | +# DEVICE:COMMENT-BLOCK:FIXME:UPSRW: ups |
| 54 | +# [battery.charge.low] |
| 55 | +# Remaining battery level when UPS switches to LB (percent) |
| 56 | +# Type: STRING |
| 57 | +# Maximum length: 10 |
| 58 | +# Value: 10 |
| 59 | +# |
| 60 | +# [battery.mfr.date] |
| 61 | +# Battery manufacturing date |
| 62 | +# Type: STRING |
| 63 | +# Maximum length: 10 |
| 64 | +# Value: 2022/12/13 |
| 65 | +# |
| 66 | +# [battery.runtime.low] |
| 67 | +# Remaining battery runtime when UPS switches to LB (seconds) |
| 68 | +# Type: STRING |
| 69 | +# Maximum length: 10 |
| 70 | +# Value: 120 |
| 71 | +# |
| 72 | +# [input.sensitivity] |
| 73 | +# Input power sensitivity |
| 74 | +# Type: STRING |
| 75 | +# Maximum length: 10 |
| 76 | +# Value: medium |
| 77 | +# |
| 78 | +# [input.transfer.high] |
| 79 | +# High voltage transfer point (V) |
| 80 | +# Type: STRING |
| 81 | +# Maximum length: 10 |
| 82 | +# Value: 266 |
| 83 | +# |
| 84 | +# [input.transfer.low] |
| 85 | +# Low voltage transfer point (V) |
| 86 | +# Type: STRING |
| 87 | +# Maximum length: 10 |
| 88 | +# Value: 180 |
| 89 | +# |
| 90 | +# [ups.delay.shutdown] |
| 91 | +# Interval to wait after shutdown with delay command (seconds) |
| 92 | +# Type: STRING |
| 93 | +# Maximum length: 10 |
| 94 | +# Value: 20 |
| 95 | +# DEVICE:EOC |
| 96 | + |
| 97 | +# DEVICE:COMMENT-BLOCK:FIXME:UPSCMD: ups |
| 98 | +# Instant commands supported on UPS [ups]: |
| 99 | +# |
| 100 | +# beeper.disable - Disable the UPS beeper |
| 101 | +# beeper.enable - Enable the UPS beeper |
| 102 | +# beeper.mute - Temporarily mute the UPS beeper |
| 103 | +# beeper.off - Obsolete (use beeper.disable or beeper.mute) |
| 104 | +# beeper.on - Obsolete (use beeper.enable) |
| 105 | +# load.off - Turn off the load immediately |
| 106 | +# load.off.delay - Turn off the load with a delay (seconds) |
| 107 | +# shutdown.reboot - Shut down the load briefly while rebooting the UPS |
| 108 | +# shutdown.stop - Stop a shutdown in progress |
| 109 | +# test.battery.start.deep - Start a deep battery test |
| 110 | +# test.battery.start.quick - Start a quick battery test |
| 111 | +# test.battery.stop - Stop the battery test |
| 112 | +# test.panel.start - Start testing the UPS panel |
| 113 | +# test.panel.stop - Stop a UPS panel test |
| 114 | +# DEVICE:EOC |
| 115 | + |