Share and synchronize data between multiple Siemens S7-1200 PLCs through a lightweight Node.js intermediary.
Instead of the traditional Siemens PUT/GET mesh where every PLC talks directly to every other PLC, this server acts as a central hub. It reads a shared data block from each PLC and writes the combined dataset back into a synchronization data block on every PLC, so each PLC has a real-time snapshot of all the others. A web GUI, an HTTPS JSON API and optional MQTT integration are included.
- Multi-PLC data sharing and synchronization through one intermediary.
- HTTPS JSON API for monitoring combined data, per-PLC data and read/write counters.
- Single JSON configuration file (JSONC, so comments are allowed).
- Automatic calculation of synchronization offsets.
- Web GUI for visualization, configuration and control.
- Field Manager: add or remove shared fields across all PLCs from one place. It recomputes every offset and generates importable TIA
.dbexternal-source files, so the three edit sites stay consistent. - Pause/Resume sync: suspend only the cross-PLC sync writes during a DB layout change, without stopping the process.
- Rotating log files, Basic authentication (bcrypt), and a built-in manual.
- Optional MQTT publish and subscribe.
- Node.js 18+ (v12+ works, 18+ recommended).
- Siemens S7-1200 PLCs with PUT/GET communication enabled.
- The relevant Data Blocks must have optimized block access disabled (absolute addressing).
- A process manager such as PM2 (recommended).
git clone https://github.com/nrbrt/s7_sync_server.git
cd s7_sync_server
npm install
# create your own config and credentials from the examples
cp config.example.json config.json
cp credentials.example.json credentials.json
# generate a bcrypt hash for the admin password, then paste it into credentials.json
node createhash.jsProvide TLS material in certs/ (cert.pem + key.pem); a self-signed pair is fine on a trusted network. Then start it:
npm start # runs: node sws5.js
# or under a process manager:
pm2 start sws5.js --name plc-syncEverything lives in config.json. Start from the fully commented config.example.json. Because the loader parses JSONC, comments are allowed in your live config.json too. Key sections:
httpPort,operationInterval(ms between update cycles),maxReconnectAttempts,reconnectInterval.apiConfig: base URL and endpoint paths the web GUI uses to reach the server.plcs[]: one entry per PLC, withname,ip,rack,slot,dbNumber(the PLC's shared block),syncDbNumber(the combined sync DB), andvariables.- Variable descriptors:
BOOLuses{ "type": "BOOL", "byte": N, "bit": N };INTandREALuse{ "type": "INT", "offset": N }(INTis 2 bytes,REALis 4 bytes).
- Variable descriptors:
mqttConfigs[]: optional brokers, each withbrokerUrl, an optionalsubscribeTopicsmap ({ dataType, syncVariable }per topic), and apublishTopic. Leave the array empty if you do not use MQTT.
config.json is the single source of truth for field names.
The server runs over HTTPS with Basic authentication, so every call uses https:// and -u user:password.
| Method and path | Purpose |
|---|---|
GET /data |
Heartbeat, combined PLC data and counters (JSON). |
GET /status |
Server and per-PLC status. |
GET /plc/<name> |
Latest data from one PLC. |
POST /plc/<name> |
Write variables to a PLC (JSON body { "var": value }). |
GET /gui, /setup, /fields, /manual |
Web pages. |
POST /config |
Replace the configuration (backs up to config.json.bak, takes effect on restart). |
POST /fields/preview |
Compute the new config and .db artifacts for an add/remove, without writing. |
POST /sync/pause, /sync/resume, GET /sync/status |
Pause or resume only the cross-PLC sync writes. |
POST /update-credentials |
Change the login username and password. |
POST /restart |
Exit gracefully so the process manager restarts it. |
GET /logs, GET /logs/<file> |
List logs, or read the last 100 lines of one. |
GET /logout |
Force a credentials re-prompt. |
Examples:
curl -k -u admin:yourpassword https://your-server:3011/data
curl -k -X POST https://your-server:3011/plc/PLC_1 \
-u admin:yourpassword -H "Content-Type: application/json" \
-d '{"machine_running": true, "current_speed": 1200}'Each cycle the server reads every PLC's shared block and writes the combined dataset into the sync DB (the DB200 convention) on every PLC, plus a heartbeat the PLCs watch to confirm the data is fresh. Per-PLC reachable and alive status is tracked.
The server attaches no meaning to field names or values. It simply transports each PLC's shared bytes to every other PLC, so you are free to structure the shared data however you like.
As one example of coordinating over the shared data, fields can use three suffixes. Each field is written by the PLC in whose share_this_data it lives and read by the others through the sync DB:
_req/_request: the desired state or value, written by the requesting PLC. It may carry a setpoint (for examplepump_a_speed_requestas an INT) or be a simple on/off BOOL._ack(BOOL): also written by the requesting PLC.falsemeans a request is open or in progress;truemeans the executor has reached the requested state._state/_stat: the actual current state or feedback, written by the executing PLC.
Flow: the requester writes _req and sets _ack = false, which opens the request. The executor drives its output toward _req and reflects it in _state. The requester sets _ack = true once _state matches _req, which closes the handshake. It is level-based and tolerant of the cyclic sync latency: while _ack stays false the executor keeps driving toward _req. Multiple requesters each use their own _req/_ack pair, so independent requests run as parallel handshakes.
Example: to start a pump on PLC_B, PLC_A sets pump_a_req = true and pump_a_ack = false. PLC_B sees the open request, runs the pump and publishes pump_a_state = true. PLC_A sees the state match its request and sets pump_a_ack = true.
A shared field lives in three places that must stay consistent: the source PLC's share_this_data DB, the combined sync DB on every PLC, and the offsets in config.json. The Field Manager (/fields) automates this. Pick a PLC, add (one or several) or remove a field, and it recomputes all offsets and generates the importable TIA .db external-source files (share_this_data.<PLC>.db and synced_data.db) plus the updated config.json.
Each preview reports whether the change is hot-safe. Only appending a field to the last PLC in config order is truly hot-safe (nothing shifts in the sync DB). Adding to any other PLC shifts every downstream PLC's offset, and removing repacks the block; both relocate live data, so they need a coordinated rollout.
Recommended workflow for a layout change:
- In the Field Manager, make the change and click Replace config.json (the running server keeps syncing on its old in-memory config, and the old file is saved as
config.json.bak). Download the generated.dbfiles. - On the Setup page, click Pause Sync right before touching the PLCs, to keep the disruption window short.
- In TIA, import the new
share_this_data.<PLC>.dbinto each edited PLC and the newsynced_data.dbinto all PLCs. - Restart the server. The new
config.jsonloads and, because a restart clears the pause flag, syncing resumes automatically on the new consistent layout.
For each configured broker the server subscribes to the defined topics (merging incoming values into the shared dataset according to their dataType) and, each cycle, publishes a JSON payload containing the server heartbeat, the combined PLC data, and any MQTT-sourced data to the configured publishTopic.
The server writes daily-rotated info and error logs (plc-app-*.log, plc-errors-*.log). Browse them through /logs or the Setup page.
- Connection issues: verify the PLC IP, rack, slot and PUT/GET settings, and make sure the network allows TCP port 102.
- Data not syncing: confirm the DBs are not optimized and that absolute addressing is configured.
- Heartbeat stagnant: confirm the PLC logic is running and that the correct DB address is read.
- Reachable but not alive: if the server connects but the PLC appears unresponsive, verify the PLC's heartbeat-updating logic.