Connecting FHEM to ip4knx — without knxd

ip4knx is itself a full KNXnet/IP gateway (Routing and Tunneling). FHEM speaks KNXnet/IP natively through its KNXIO I/O module, so it can talk to ip4knx directly — no knxd in between.

The FHEM wiki puts it plainly: "If a KNX-Gateway supports multicast, you don't need a knxd installation." The same holds for tunneling.

Why drop knxd?

  • One less service and one less failure layer between FHEM and the bus.
  • KNXIO has its own connection-state heartbeat + auto-reconnect (tunneling) and needs no extra daemon.
  • Fewer moving parts to configure, restart, and keep in sync.

Prerequisites

  • The stick must be running the ip4knx firmware — that is what turns it into a KNXnet/IP gateway. A plain serial-bridge firmware will not work here: it speaks no KNXnet/IP, which is exactly why such setups need knxd. Flash ip4knx straight from the browser with the web flasher at https://install.busware.de/ip4knx/ (Chrome / Edge / Opera); it also walks you through Wi-Fi provisioning (Improv) in the same flow, and can update an existing device later. Other install options (esptool, PlatformIO) are in the README.

  • Once the stick is on Wi-Fi, note its IP address — from the built-in dashboard, mDNS (http://tul.local), or your router's lease list.

  • A current FHEM. The required modules — KNXIO (I/O, file 00_KNXIO.pm) and KNX (device, 10_KNX.pm) — ship with FHEM out of the box.

    The legacy EIB / TUL / KNXTUL modules are not needed (and EIB no longer exists in current FHEM). Use KNX + KNXIO.

Step 1 — Define the I/O (KNXIO)

Recommended: Mode H (Host / Tunneling) — unicast UDP, the same protocol ETS uses.

define KNXGW KNXIO H <IP-OF-IP4KNX>:3671 <FREE-IA>
  • <IP-OF-IP4KNX> — the address shown on the dashboard; 3671 is the standard KNXnet/IP port.
  • <FREE-IA> — an individual address for FHEM, e.g. 1.1.250. With tunneling this is uncritical: ip4knx assigns each tunnel its own individual address and rewrites the source address of outgoing frames (KNXnet/IP Core §4.4), so it cannot clash with real bus devices. It only has to be a syntactically valid address.

Check it came up:

list KNXGW

STATE should read connected. On the ip4knx dashboard the active tunnel/client count goes to 1.

Alternative — Mode M (Multicast / Routing):

define KNXGW KNXIO M 224.0.23.12:3671 <FREE-IA>

224.0.23.12:3671 is the standard KNX routing multicast group. Caveat: routing does not rewrite the source address, so <FREE-IA> must be a genuinely free, unique address in your ETS project — otherwise you create a bus address conflict. Multicast delivery to a Wi-Fi client can also be less reliable than a unicast tunnel, so Mode H is the recommended default for a Wi-Fi gateway.

Timing note (from the FHEM KNXIO wiki, applies to Mode H): the tunneling protocol is timing-sensitive — FHEM delays larger than ~1 second can drop the connection. Recovery is automatic (KNXIO reconnects), though a few messages may be lost across the reconnect.

Step 2 — Define a KNX device

Point a device at a group address and its datapoint type. For a simple switch (1-bit, DPT 1):

define myLight KNX <MAIN>/<MIDDLE>/<SUB>:dpt1

Example:

define myLight KNX 1/2/3:dpt1

Now control it:

set myLight on
set myLight off
set myLight toggle

If you run more than one KNXIO I/O, pin the device explicitly: attr myLight IODev KNXGW.

Verifying it works

  • Send: set myLight on — the ip4knx dashboard's TX counter increments (each group write is one L_Data frame on the bus).
  • Receive: operate the load from a physical KNX switch/actuator — the RX counter increments and the FHEM device state follows automatically.

That round-trip — command out, external change reflected back — confirms the direct, knxd-free path works in both directions.

Mode reference

KNXIO mode Connects to knxd needed?
H (Host) KNXnet/IP Tunneling (unicast) → ip4knx directly No
M (Multicast) KNXnet/IP Routing (multicast) → ip4knx directly No
T (TCP) knxd via TCP (:6720) Yes
S (Socket) knxd via UNIX socket Yes

Only H and M talk to a gateway directly; T and S are knxd back-ends.

Troubleshooting

  • KNXIO STATE not connected: verify the ip4knx IP and that UDP port 3671 is reachable from the FHEM host (same subnet / no firewall in between).
  • Address conflict on the bus (Mode M): pick a <FREE-IA> that no real device uses. Mode H avoids this via source-address rewrite.
  • Connection drops after some time: isolate the side at fault first — power-cycle only the ip4knx stick and leave FHEM running. If it recovers on its own, the fault is on the gateway/Wi-Fi side (check Wi-Fi signal and your router's DHCP lease time); if only a FHEM restart helps, the fault is on the host side.

Reference